Specification
| Standard |
IEC/BS/EN62606,IEC/AS/NZS 61009.1 (RCBO) |
| Rated current |
6,10,13,16,20,25,32,40A |
| Rated voltage |
230/240V AC |
| Rated frequency |
50/60Hz |
| Maximum operating voltage |
1.1Un |
| Minimum operating voltage |
180V |
| Protection degree |
IP20 /IP40 (Terminals/Housing) |
| Type & mounting arrangement |
Din-Rail |
| Application |
Consumer unit |
| Tripping curve |
B,C |
| Rated residual making and breaking capacity (I△m) |
2000A |
| Mechanical operations |
>10000 |
| Electrical operations |
≥1200 |
| Rated residual operating current (I△n) |
10,30,100,300mA |
| Rated short-circuit capacity (Icn) |
6kA |
| AFDD Test means |
Automatic test function as per 8.17 IEC 62606 |
| Classification as per IEC 62606 |
4.1.2 - AFDD unit integrated in a protective device |
| Ambient operating temperature |
-25°C to 40°C |
| AFDD ready indication |
Single LED Indication |
| Overvoltage function |
Overvoltage condition of 270Vrms to 300Vrms for 10 seconds will cause device to trip.LED indication of over-voltage trip will be provided on product re-latch. |
| Self test interval |
1 Hour |
| Earth fault current |
Trip time limit (typical measured value) |
| 0.5 x Idn |
No trip |
| 1 x Idn |
<300 ms (nominally <40 ms) |
| 5 x Idn |
<40ms (nominally <40 ms)Actual Tripping Threshold |
Operation and Display
■LED Indication:
□After tripping under a fault condition the fault status indicator will show the fault nature according to the table opposite.
□LED flashing sequence repeats every 1.5sec for next 10 sec after powering up
■Series Arc Fault:
□1 Flash - Pause - 1 Flash - Pause - 1 Flash
■Parallel Arc Fault:
□1 2 Flashes - Pause - 2 Flashes - Pause - 2 Flashes
■Over Voltage Fault:
□3 Flashes - Pause - 3 Flashes - Pause - 3 Flashes
■Self-Test Fault:
□1 Flash - Pause -1 Flash - Pause -1 Flash (At Double Rate)