| Rated Current Range (InA) | Max consumption/pole (W) |
| In≤10 | 3 |
| 10<In≤16 | 3.5 |
| 16<In≤25 | 4.5 |
| 25<In≤32 | 6 |
| 32<In≤40 | 7.5 |
| 40<In≤50 | 9 |
| 50<In≤63 | 13 |
| Test Current | Type | Test procedure | Initial State | Tripping or Non-tripping Time Limit | Expected Result | Remark |
| A | B,C,D | 1.13In | cold | t≤1h | no tripping | |
| B | B,C,D | 1.45In | after test a | t<1h | tripping | Current in the 5s in th increase of stability |
| C | B,C,D | 2.55In | cold | 1s<t<60s(In≤32A)/1s<t<120s(n>32A) | tripping | |
| D | B | 3In | cold | t≥0.1s | no tripping | Turn on the auxiliary switch to |
| C | 5In | |||||
| D | 10In | |||||
| E | B | 5In | t<0.1s | tripping | Turn on the auxiliary switch to | |
| C | 10In | cold | ||||
| D | 20In |