  • CJRX16 Auxiliary, through a combination of different component and assembly,achieved function of Shunt tripper, under-voltage tripper, auxiliary contact, Shunt tripper + auxiliary contact and Under-voltage tripper + auxiliary contact.
  • The handles of these 5 products are designed with mid-position and without midposition.
  • The product has a transparent clamshell to put tags in and characteristic stripes on both sides.
  • It is featured with elegant appearance, complete function and small volume.
  • In same housing, through a combination of different component and assembly,achieved auxiliary contact、remote shunt trip and under-voltage protect.
 

Shunt tripper

  • Rated voltage: AC 230V
  • Moving voltage: (70%~110%) x Ue
 

Under-voltage tripper

  • Rated voltage: AC 230V
  • Moving voltage: (35%~70%) x Ue
  • Guaranteed closing voltage: (85%~110%) x Ue
 

Outline and Mounting Dimension

Auxiliary Contact

1NO+1NC (1 normal open+ 1 normal close)
Usage category Rated current (A) Rated Voltage(V)
AC12 3 400
6 230
DC12 6 24
2 48
1 130